Description
Technical Specifications
-
Product Type: Digital Relay & Remote Alarm Board
-
Part Number: DS3800DRRA
-
Manufacturer: General Electric (GE)
-
System Compatibility: GE Speedtronic Mark IV Turbine Control Systems
-
Output Channels: 16 digital outputs (Form C – SPDT relays)
-
Contact Rating: 5A @ 250VAC or 5A @ 30VDC (resistive); 3A @ 250VAC (inductive)
-
Surge Suppression: Built-in RC snubbers and flyback diodes per channel
-
Indicators: Front-panel LEDs per channel (no mechanical flags)
-
Isolation: 2500Vrms opto-isolation (logic-to-field) with reinforced insulation for remote wiring
-
Terminal Connections: 34-pin edge connector + dedicated screw terminal block for field wiring
-
Temperature Range: -40°C to +70°C
-
MTBF: > 180,000 hours (MIL-HDBK-217F)
Key Features & Advantages
-
Remote Signaling Optimized: The GE DS3800DRRA is designed for driving loads over long cable runs (up to 1000 meters), with higher surge suppression and isolation to handle induced voltages and ground potential differences common in plant-wide systems.
-
No Mechanical Flags: Unlike the DS3800DRFA series, the DS3800DRRA uses LEDs only. This reduces mechanical wear and is acceptable for remote panels where physical flag indication is not required.
-
Higher Inductive Load Rating: Rated for 3A inductive (vs. 2A on the DS3800DRFA), making it suitable for driving medium-sized contactors and solenoids in remote junction boxes.
-
Reinforced Isolation: 2500Vrms with reinforced insulation ensures reliable communication between the Mark IV rack and remote equipment, even with significant ground potential differences.
-
Screw Terminal Block: The GE DS3800DRRA includes a dedicated terminal block for field wiring, simplifying installation and maintenance compared to edge-connector-only boards.
-
Fast Response: Typical relay switching time < 10ms, suitable for alarm annunciation and critical signaling.
Typical Application Cases
-
Remote Alarm Annunciation: The GE DS3800DRRA sends turbine status signals (e.g., overspeed, high temperature, low pressure) to the plant DCS or central control room alarm panels. Each channel corresponds to a specific alarm condition.
-
Interfacing with Plant DCS: In combined-cycle power plants, the GE DS3800DRRA provides dry relay contacts to the DCS (e.g., Emerson Ovation, ABB 800xA) for turbine status monitoring and coordinated plant control.
-
Remote Shutdown Signaling: Sends turbine trip signals to emergency shutdown systems (ESD) in adjacent units, enabling plant-wide safety interlocks.
-
Indication Panel Driving: In older plants, the GE DS3800DRRA drives the large mimic panels in the control room that display turbine operating status.
-
Data Logging Triggers: Provides contact closures to data loggers and event recorders, capturing turbine events for post-trip analysis.
Competitive Comparison
| Feature | GE DS3800DRRA | GE DS3800DRFA (Flag Board) | Modern DCS Output Module |
|---|---|---|---|
| Primary Purpose | Remote signaling / DCS interface | Local actuator control + visual flags | Remote I/O (fieldbus) |
| Visual Indication | LEDs only | Mechanical flags + LEDs | LEDs only (software status) |
| Contact Rating (Inductive) | 3A @ 250VAC | 2A @ 250VAC | 0.5A @ 24VDC (typical) |
| Isolation | 2500Vrms reinforced | 2500Vrms | 500Vrms |
| Terminal Type | Screw terminal block | Edge connector only | Spring clamp or pluggable |
| Latching Relays | No (standard relays) | Yes (magnetic latching) | No |
| Temperature Range | -40°C to +70°C | -40°C to +70°C | 0°C to +60°C |
| Compatibility | Dedicated Mark IV | Dedicated Mark IV | Universal fieldbus |
The GE DS3800DRRA bridges the gap between the legacy Mark IV system and modern plant DCS architectures. While modern DCS output modules offer digital communication and advanced diagnostics, they require protocol converters and cannot directly interface with the Mark IV backplane. The GE DS3800DRRA remains the most reliable solution for hardwired signal transfer from the turbine control system to the plant-wide automation network.
Selection Guidelines & Precautions
-
Cable Length and Voltage Drop: When using the GE DS3800DRRA for long-distance signaling ( > 500m ), verify that the voltage drop across the cable does not exceed the minimum pull-in voltage of the remote device. For 24VDC circuits, maintain cable resistance below 10Ω per contact to ensure reliable operation.
-
Ground Potential Differences: The GE DS3800DRRA provides 2500Vrms isolation, but if ground potential differences exceed this rating (rare), install additional isolation relays or optical isolators at the remote end to protect the board.
-
No Mechanical Flags: Unlike the DS3800DRFA, the GE DS3800DRRA does not provide latching mechanical flags. For critical trip circuits that require a visual record of alarm history, we recommend installing external latching relays or using the DS3800DRFA board instead.
-
Terminal Block Wiring: Use ferrules on all stranded wires terminated on the GE DS3800DRRA terminal block to prevent loose connections. Loose wiring can cause intermittent signals and nuisance alarms.
-
Inductive Load Derating: For inductive loads exceeding 3A, use the GE DS3800DRRA to drive an external interposing relay. This protects the board’s contacts from welding and extends its operational life.
-
Shielded Cabling: We recommend shielded twisted-pair cable for all remote wiring connected to the GE DS3800DRRA. Ground the shield at one end (typically the DCS side) to prevent ground loops while maintaining noise immunity.
-
Backplane Compatibility: The GE DS3800DRRA is compatible with Mark IV backplanes Rev. L and later. Verify pin assignments before installation; some early racks require a pin adapter for the reinforced isolation circuits.
-
Lifecycle Sourcing: The GE DS3800DRRA is obsolete and available only through aftermarket suppliers. When purchasing, request:
-
Functional test report (all 16 channels tested under rated load)
-
Contact resistance measurement (< 0.1Ω new, < 0.5Ω refurbished)
-
Surge suppression verification (RC snubber and flyback diode functionality)
-
Visual inspection for burnt contacts or overheated solder joints
-
Electrolytic capacitor replacement (if aged > 10 years)
-
-
Spare Strategy: Keep at least one spare GE DS3800DRRA on-site. For critical alarm circuits (e.g., fire detection, overspeed), consider redundant configuration with two boards and remote relays in series to ensure fail-safe operation

A-B 1794-ACN15
NI SCXI-1300
A-B 1756-A7
YASKAWA JAMSC-B2605V