GE IS200TTPWG1B

¥999.00

IS200TTPWG1B is a Terminal Board within the GE Mark VIe Speedtronic control system, designed as a field termination and signal conditioning interface for thermocouple and pressure transducer inputs in turbine control applications. This board provides centralized termination for thermocouple sensors (J, K, T, E, R, S, B) as well as 4–20 mA or voltage pressure transducer signals, combining temperature and pressure monitoring in a single board. The IS200TTPWG1B features integrated termination points with built-in signal conditioning including cold-junction compensation (CJC) for thermocouples, excitation for transducers, filtering, enhanced isolation, and diagnostics. It offers 16 mixed input channels (configurable as thermocouple or pressure transducer), making it ideal for applications requiring both temperature and pressure monitoring.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TTPWG1B
Total Channels 16 mixed inputs (configurable per channel)
Thermocouple Inputs Up to 16 channels (J, K, T, E, R, S, B)
Pressure Transducer Inputs Up to 16 channels (4–20 mA, 0–10 V, ±10 V selectable)
Thermocouple Range ±100 mV
Transducer Range 0–20 mA, 4–20 mA, 0–5 V, 0–10 V, ±10 V
Cold-Junction Compensation Built-in CJC sensor (accuracy ±0.5°C)
ADC Resolution 24-bit delta-sigma (thermocouple), 16-bit SAR (transducer)
Sampling Rate 4–200 SPS (thermocouple), 10–500 SPS (transducer)
Accuracy (TC) ±0.1% of reading + ±1°C
Accuracy (Transducer) ±0.1% FS
Transducer Loop Power 24 VDC (externally supplied only)
Isolation 1500 VAC (field-to-system)
CMRR >100 dB @ 50/60 Hz
Diagnostics Open-circuit detection, short-circuit detection, CJC fault monitoring, over/under-range detection, loop power fault monitoring
Status Indication 16 green LEDs (channel active), 2 red LEDs (diagnostic fault summary)
Operating Temperature –30°C to +65°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connectors
Backplane Interface VME64x (A24/A32, D16/D32/D64)
EMC Compliance IEC 61000-4 Level 4

Advantages & Key Features

  • Mixed Input FlexibilityIS200TTPWG1B combines thermocouple and pressure transducer inputs on a single board, eliminating the need for separate terminal boards for temperature and pressure monitoring.

  • Configurable Channel Allocation: Each channel can be independently configured as thermocouple or pressure transducer via GE ToolboxST, matching specific application requirements.

  • High Channel Density: 16 mixed inputs in a single VME slot—double the density of competing modules.

  • High-Precision CJC: Built-in CJC sensor with automatic compensation ensures thermocouple measurement accuracy.

  • 24-Bit Thermocouple Conversion: High-resolution ADC delivers stable, noise-free temperature readings.

  • Programmable Transducer Inputs: Each transducer channel supports 4–20 mA, 0–10 V, or ±10 V inputs.

  • Comprehensive Diagnostics: Open-circuit, short-circuit, CJC fault, over/under-range, and loop power fault detection per channel.

  • Opto-Isolation: 1500 VAC isolation protects the Mark VIe backplane from field wiring faults.

  • ToolboxST Integration: Full configuration, calibration, and diagnostics via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for earlier GE mixed thermocouple/transducer terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Exhaust gas temperature (thermocouple) combined with fuel gas pressure (4–20 mA), steam pressure (4–20 mA), and bearing temperature (thermocouple).

  • Combined Cycle Plants: HRSG superheater temperature (thermocouple) plus steam drum pressure (4–20 mA) and feedwater flow (4–20 mA).

  • Compressor Stations: Discharge temperature (thermocouple) combined with suction/discharge pressure (4–20 mA).

  • Aeroderivative Turbines: Exhaust temperature (thermocouple) plus fuel flow (4–20 mA) and oil pressure (4–20 mA).

Comparison with Competing Products

Feature GE IS200TTPWG1B Competitor A (Mixed TC/Transducer) Competitor B (Separate TC + Transducer)
Total Inputs 16 mixed 8 mixed 16 (8 TC + 8 transducer)
Thermocouple Types J, K, T, E, R, S, B J, K, T J, K, T, E, R, S, B
CJC Accuracy ±0.5°C ±1.2°C ±0.5°C
Transducer Accuracy ±0.1% FS ±0.2% FS ±0.1% FS
Isolation 1500 VAC 1000 VAC 1500 VAC
Operating Temp –30°C to +65°C 0°C to 50°C –30°C to +65°C

Key AdvantageIS200TTPWG1B provides 16 mixed thermocouple/transducer inputs—double the density of competing mixed modules—with high-precision CJC and comprehensive diagnostics, making it ideal for turbine applications requiring both temperature and pressure monitoring.

Selection Guidelines & Recommendations

  • Channel Configuration: Determine required mix of thermocouple and transducer inputs—configure each channel in GE ToolboxST.

  • Thermocouple Type: Select J, K, T, E, R, S, or B per channel.

  • Transducer Type: Configure 4–20 mA, 0–10 V, or ±10 V per channel.

  • Transducer Loop Power: External 24 VDC supplies required—plan cabinet power distribution.

  • CJC Sensor Placement: Maintain adequate airflow around the CJC sensor on the terminal block.

  • Controller Firmware: Requires Mark VIe processor firmware v7.5 or later.

  • Wiring Guidelines: Use shielded thermocouple extension-grade leads and twisted-pair cables for transducers.

  • Spare Strategy: Keep one spare per turbine; lead times 6–10 weeks.

  • Retrofit: Direct replacement—regenerate configuration in GE ToolboxST.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. Thermocouple Polarity: Reverse connection produces negative readings—verify polarity.

  3. Transducer Polarity: Observe correct polarity for 4–20 mA loops and voltage inputs.

  4. CJC Protection: Do not apply conformal coating or tape over the terminal block area.

  5. Transducer Loop Power: External 24 VDC required—ensure supplies are connected.

  6. Grounding: Connect AGND to Mark VIe system ground at single star point.

  7. Shield Termination: Ground shields only at cabinet end.

  8. ESD Handling: Use grounded wrist straps; field repair not possible.

  9. Channel Mapping: With 16 mixed channels, verify field wiring maps to correct ToolboxST assignments.

  10. Input Overload: Sustained transducer input >30 V or >50 mA may damage input circuitry.

SIEMENS E3L020 546645
A-B 1756-A10
A-B 1794-ASB
A-B 1756-PA75

Reviews

There are no reviews yet.

Be the first to review “GE IS200TTPWG1B”

Your email address will not be published. Required fields are marked *

Post comment