GE IS200TPROH2CBB

¥999.00

IS200TPROH2CBB is an advanced high-channel-density Terminal Board within the GE Mark VIe Speedtronic control system, designed as a field termination and signal conditioning interface for speed probe and proximity probe inputs with the highest channel capacity, highest accuracy, comprehensive diagnostics, and advanced calibration management. This board provides centralized termination for speed sensors such as magnetic pickups, proximity probes, and other frequency-output devices used for turbine shaft speed monitoring, overspeed detection, and speed control. The IS200TPROH2CBB features integrated termination points for speed inputs with built-in signal conditioning including filtering, enhanced isolation, and surge protection. It offers up to 6 independent speed input channels—the highest channel count in the Mark VIe speed probe terminal family—with programmable scaling, frequency measurement, enhanced diagnostics including signal integrity monitoring, sensor drift detection, and comprehensive calibration features.

Category:

Description

Product Parameters

Parameter Specification
Brand / Series GE Mark VIe Speedtronic
Model IS200TPROH2CBB
Speed Inputs Up to 6 independent channels (configurable)
Input Signal Types Magnetic pickups, proximity probes (passive/active), TTL, 5–24 VDC logic
Frequency Range 0.5 Hz – 35 kHz — upgraded from 30 kHz
Input Voltage Range ±30 VDC maximum
Input Impedance > 10 kΩ
Trigger Level Programmable per channel (0.5–24 VDC, hysteresis configurable)
Scaling Programmable (RPM, Hz, etc.) via GE ToolboxST
Accuracy ±0.005% of reading
Isolation 2000 VAC (field-to-system)
Diagnostics Open-circuit detection, signal loss detection, frequency out-of-range monitoring, signal integrity monitoring (amplitude/quality), reference validation, calibration status tracking, sensor drift detection, channel-to-channel skew detection
Status Indication 6 green LEDs (channel active), 6 red LEDs (channel fault), 2 red summary fault LEDs, 1 yellow LED (reference/calibration status), 1 blue LED (diagnostic active)
Calibration Features Onboard calibration memory with traceable records, software-triggered self-calibration, factory calibration certificate stored onboard
Operating Temperature –40°C to +70°C
Storage Temperature –55°C to +85°C
Mounting VME rack-mount terminal board with front-panel I/O connectors
Backplane Interface VME64x (A24/A32, D16/D32/D64)
EMC Compliance IEC 61000-4 Level 4

Advantages & Key Features

  • Maximum Channel Density: Up to 6 independent speed inputs in a single VME slot—the highest channel count in the Mark VIe speed probe terminal family, providing 50% more channels than IS200TPROH1C (6 channels with lower accuracy) and six times that of competing 1-channel modules. Ideal for multi-shaft turbines and complex speed monitoring applications.

  • Highest Accuracy: ±0.005% reading accuracy provides the highest precision for speed measurements.

  • Extended Frequency Range: 0.5 Hz to 35 kHz covers the widest range from startup to overspeed conditions.

  • Extended Temperature Range: –40°C to +70°C operation makes IS200TPROH2CBB suitable for extreme environments.

  • Enhanced Isolation: 2000 VAC isolation provides superior protection for the Mark VIe backplane.

  • Signal Integrity Monitoring: Per-channel amplitude/quality monitoring detects weak or degraded sensor signals.

  • Sensor Drift Detection: Tracks sensor performance over time to predict failures before they occur.

  • Channel-to-Channel Skew Detection: Detects timing mismatches between channels for precise multi-speed applications.

  • Versatile Signal Compatibility: Supports magnetic pickups, proximity probes, TTL, and logic-level signals.

  • Programmable Trigger Levels: Per-channel programmable trigger voltage and hysteresis ensure reliable detection.

  • Advanced Calibration: Onboard calibration memory with traceable records, factory certificate, and software-triggered self-calibration.

  • Comprehensive Diagnostics: Open-circuit, signal loss, frequency out-of-range, signal integrity, reference validation, sensor drift, and channel skew detection.

  • ToolboxST Integration: Full configuration, monitoring, diagnostics, and calibration management via GE ToolboxST.

  • Drop-In Replacement: Direct replacement for IS200TPROH2CIS200TPROH1C, and earlier speed probe terminal boards.

Application Fields

  • Gas & Steam Turbines (GE Frame 6B/7EA/9E/HA): Shaft speed monitoring, overspeed detection, speed control, and multi-shaft monitoring.

  • Aeroderivative Turbines: Speed monitoring and overspeed protection.

  • Compressor Stations: Compressor speed monitoring for multiple stages.

  • Generator Speed Monitoring: Turbine-generator speed measurement.

  • Multi-Shaft Applications: Speed monitoring of multiple turbine sections in combined-cycle and complex turbine configurations.

  • Arctic & Desert Installations: Extreme-environment turbine speed monitoring.

  • Nuclear Power Plants: Applications requiring maximum precision, traceable calibration, and documented records.

Comparison with Competing Products

Feature GE IS200TPROH2CBB GE IS200TPROH2C (6-ch) GE IS200TPROH1C (6-ch) GE IS200TPROH1B (4-ch) Competitor A (Speed Probe) Competitor B (Speed Monitor)
Speed Inputs Up to 6 Up to 6 Up to 6 Up to 4 2 1
Frequency Range 0.5 Hz – 35 kHz 0.5 Hz – 30 kHz 0.5 Hz – 25 kHz 0.5 Hz – 25 kHz 1 Hz – 10 kHz 1 Hz – 15 kHz
Accuracy ±0.005% ±0.005% ±0.01% ±0.01% ±0.1% ±0.05%
Signal Integrity Monitoring Yes Yes Yes Yes No No
Sensor Drift Detection Yes Yes No No No No
Channel-to-Channel Skew Detection Yes No No No No No
Reference Validation Yes Yes No No No No
Calibration Records Yes (traceable + certificate) Yes (traceable) No No No No
Self-Calibration Yes Yes No No No No
Isolation 2000 VAC 2000 VAC 2000 VAC 2000 VAC 1000 VAC 500 VDC
Operating Temp –40°C to +70°C –40°C to +70°C –40°C to +70°C –40°C to +70°C 0°C to 50°C 0°C to 60°C

Key AdvantageIS200TPROH2CBB delivers up to 6 independent speed inputs—the highest channel density in the Mark VIe speed probe terminal family—with the widest frequency range (35 kHz), highest accuracy (±0.005%), signal integrity monitoring, sensor drift detection, channel-to-channel skew detection, 2000 VAC isolation, extended –40°C to +70°C temperature range, and comprehensive calibration management including factory certificates—making it the ultimate solution for complex, high-precision turbine speed monitoring applications requiring maximum reliability and regulatory compliance.

Selection Guidelines & Recommendations

  • Input Count: Determine the number of speed inputs required—up to 6 per board.

  • Sensor Type: Verify speed sensor type and configure trigger levels in GE ToolboxST.

  • Signal Integrity Monitoring: Enable for critical speed sensors to receive early warnings.

  • Sensor Drift Detection: Enable to predict sensor failures and schedule preventive maintenance.

  • Channel Skew Detection: Enable for multi-channel applications requiring precise timing correlation.

  • Calibration Management: Use GE ToolboxST to review factory calibration certificate and perform self-calibration during scheduled maintenance.

  • Controller Firmware: Requires Mark VIe processor firmware v9.5 or later.

  • Wiring Guidelines: Use shielded twisted-pair cables. Maintain shield grounding only at the Mark VIe cabinet end.

  • Spare Strategy: Keep one spare per turbine; lead times 8–14 weeks.

  • Retrofit: Direct replacement for IS200TPROH2C and IS200TPROH1C—regenerate configuration in GE ToolboxST to access enhanced features.

Important Cautions

  1. No Hot-Swap: De-energize rack before insertion/removal.

  2. Signal Polarity: For magnetic pickups, observe correct polarity for reliable zero-crossing detection.

  3. Trigger Level: Incorrect trigger level can cause missed pulses or false triggering—verify with sensor specifications.

  4. Cable Length: For magnetic pickups, use low-capacitance cables for runs exceeding 50 meters.

  5. Grounding: Connect AGND to Mark VIe system ground at single star point.

  6. Shield Termination: Ground speed probe cable shields only at cabinet end.

  7. ESD Handling: Use grounded wrist straps; field repair not possible.

  8. Temperature Rating: Verify cabinet ambient does not exceed +70°C or fall below –40°C.

  9. Reference Validation: Yellow LED indicates reference drift—perform software self-calibration or schedule factory recalibration if illuminated.

  10. Self-Calibration: Perform only when board is de-energized and free from field wiring faults.

  11. Calibration Records: Factory calibration certificate is stored onboard. Do not modify calibration memory via external tools—use only GE ToolboxST.

  12. Signal Integrity Alerts: Investigate weak signal alerts promptly to prevent sensor failure.

  13. Sensor Drift Alerts: Investigate drift alerts to replace aging sensors before failure.

  14. Channel Skew Alerts: Investigate timing mismatches—check cable lengths and sensor alignment.

  15. Frequency Out-of-Range: Monitor diagnostic alerts—investigate sensor or wiring faults.

  16. Channel Mapping: With up to 6 channels, verify field wiring maps to correct ToolboxST channel numbers.

VICKERS DG4V-5-6CJ-M-KUP6-D2-H620
YASKAWA JACP-317800
NI SCXI-1125

Reviews

There are no reviews yet.

Be the first to review “GE IS200TPROH2CBB”

Your email address will not be published. Required fields are marked *

Post comment